Ratings per | IEC/EN 60947-7-1 |
Nominal voltage (III/3) | 800V |
Rated impulse voltage (III/3) | 8kV |
Rated current | 13,5A |
Rated current 2 | 17,5A |
Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
Approvals per | UL 1059 |
Rated voltage UL (Use Group B) | 600V |
Rated current UL (Use Group B) | 10A |
Rated voltage UL (Use Group C) | 600V |
Rated current UL (Use Group C) | 10A |
Approvals per | CSA 22.2 No 158 |
Rated voltage CSA (Use Group B) | 600V |
Rated current CSA (Use Group B) | 10A |
Rated voltage CSA (Use Group C) | 600V |
Rated current CSA (Use Group C) | 10A |
Reference hazardous areas | See Downloads – Documentation – Additional Information: Technical Section; Technical explanations |
Ratings per | ATEX: PTB 18 ATEX 1004 U / IECEx: PTB 18.0010U (Ex eb IIC Gb) |
Rated voltage EN (Ex e II) | 550V |
Rated current (Ex e II) | 13A |
Rated current (Ex e II) with jumper | 12A |
Power loss, per pole (potential) | 0,771W |
Rated current IN for specified power loss | 18A |
Resistance value for specified, current-dependent power loss | 0,002Ω |