Zile de livrare: Luni - Vineri
Data estimata de livrare: Miercuri, 29.01.2025
Product designation | Surge protection device (SPD) | |||
Product type designation | SG2 | |||
Operating voltage type | AC | |||
Application | AC Power lines | |||
Number of poles | 1P | |||
Number of DIN modules | 1 | |||
SPD according to IEC/EN 61643-11 | Yes | |||
Electrical features | ||||
IEC Maximum continuous voltage Uc | V | 300 | ||
IEC Maximum discharge current Imax 8/20 (L-N/N-PE) | kA | 50 | ||
IEC Rated discharge current (IEC) In 8/20 (L-N/N-PE) | kA | 20 | ||
IEC Voltage protection level Up (L-N/N-PE) | kV | <1.5 | ||
IEC Follow current If (N-PE) rms | A | No | ||
Tripping time ta (L-N/N-PE) | ns | <25 | ||
Thermal insulation protection | Yes | |||
IEC Backup protection fuse with supply fuse >315A (L-N/N-PE) | Class/A | 315A / 250A Gg | ||
IEC Maximum short circuit current at 50Hz | kA | 25 / 50 | ||
Status indicator - operating / end of life | Frontal indication |